The Régie du Bâtiment du Quebec (RBQ) inspection frequency table is applicable for equipment operating in Quebec.
Object Description | External Maximum Period between inspections | Internal Maximum Period between inspections |
Pressure cooker with a quick release (except for sterilizers) | 1 year | 1 year |
Hot water boiler | 2 years | – |
Thermal fluid boiler | 4 years | – |
Lower pressure steam boiler (*) | 1 year | 3 years |
High pressure steam boiler (**) | 1 year | 1 year |
Water heater | 2 years | – |
Deaerator (**) | 2 years | 2 years |
Steam Generator | 2 years | 2 years |
Digestor | 2 years | – |
Tank containing a non-corrosive fluid | 4 years | – |
Compressed air tank | 4 years | – |
Hot water tank | 4 years | – |
Expansion tank | 4 years | – |
Drying roller | 2 years | – |
Refrigeration system using refrigerant other than A1 or B1 | 2 years | – |
Any other type of pressure vessel | 4 years | – |
(*) The external periodic inspection must be made every year except for the year in which an internal inspection is made.
(**) The internal and external periodic inspection is made alternately for such equipment.