RBQ (QC) Inspection Frequency Table

RBQ Inspection Frequency Table

The Régie du Bâtiment du Quebec (RBQ) inspection frequency table is applicable for equipment operating in Quebec.

Object DescriptionExternal
Maximum Period between inspections
Internal
Maximum Period between inspections
Pressure cooker with a quick release (except for sterilizers)1 year1 year
Hot water boiler2 years
Thermal fluid boiler4 years
Lower pressure steam boiler (*)1 year3 years
High pressure steam boiler (**)1 year1 year
Water heater2 years
Deaerator (**)2 years2 years
Steam Generator2 years2 years
Digestor2 years
Tank containing a non-corrosive fluid4 years
Compressed air tank4 years
Hot water tank4 years
Expansion tank4 years
Drying roller2 years
Refrigeration system using refrigerant other than A1 or B12 years
Any other type of pressure vessel4 years

(*) The external periodic inspection must be made every year except for the year in which an internal inspection is made.

(**) The internal and external periodic inspection is made alternately for such equipment.